3-130 UR FAMILY – COMMUNICATIONS GUIDE
MODEL IMPLEMENTATION CONFORMANCE STATEMENT (MICS) CHAPTER 3: IEC 61850 COMMUNICATION
3
3.5.3.17 Incipient cable fault detection (ICFlt)
This element is instantiated in the following products: D30, F35, F60, L30.
Table 3-155: Incipient fault detector data objects
LNName: ICFltPTEF# LDevice inst: Ctrl UR element: Incipient Cable Fault Element #
data obj. data attribute Type FC UR Name Description R/W/C
Mod INC This logical node’s mode R/Ctrl
stVal ENUMERATED ST 1 (on) R
ctlModel CtlModels CF 0 (status only) R
Health INS This logical node’s health R
stVal ENUMERATED ST LPHD1.PhyHealth.stVal R
Str ACD INCIPNT FLT # PKP operands (including
individual three phases)
R
general BOOLEAN ST INCIPNT FLT # PKP R
dirGeneral ENUMERATED ST 0 R
phsA BOOLEAN ST INCIPNT FLT # PKP A R
dirPhsA ENUMERATED ST 0 R
phsB BOOLEAN ST INCIPNT FLT # PKP B R
dirPhsB ENUMERATED ST 0 R
phsC BOOLEAN ST INCIPNT FLT # PKP C R
dirPhsC ENUMERATED ST 0 R
Op ACT INCIPNT FLT # OP operands (including
individual three phases)”
R
general BOOLEAN ST INCIPNT FLT # OP R
phsA BOOLEAN ST INCIPNT FLT # OP A R
phsB BOOLEAN ST INCIPNT FLT # OP B R
phsC BOOLEAN ST INCIPNT FLT # OP C R
FltCntPhφ INS INCIPIENT FAULT # PH θ FAULTS R
stVal INT32 ST INCIPIENT FAULT # PH θ FAULTS R
units Unit CF R
units.SIUnit ENUMERATED 1 R
units.multiplier ENUMERATED 0 R
FltCntClr SPC Only instantiated in ICFltPTEF1 R/Ctrl
pulseConfig PulseConfig CF R
pulseConfig
.cmdQual
ENUMERATED 0 (pulse) R
pulseConfig.onDur INT32U 2 R
pulseConfig
.offDur
INT32U 0 R
pulseConfig
.numPls
INT32U 1 R
ctlModel CtlModels CF ICFltPTEF#.FltCntClr.ctlModel R/W/C
sboTimeout INT32U CF 30000 R
sboClass SboClasses CF 0 (operate-once) R
operTimeout INT32U CF 0 R
BlkRef1 ORG INCIPNT FLT # BLOCK setting R
GEORG R
setSrcRef ObjectReference SP INCIPNT FLT # BLOCK. reference to the data attribute to input R/C
VISIBLE
STRING255
SP Reference to the ultimate source
of value selected by setting
INCIPNT FLT # BLOCK.
R/C
setSrcCB ObjectReference SP source GoCB of input if via GOOSE R/C
VISIBLE
STRING255
SP If reference is external to this
IED, mapped to the source’s
GOOSE control block, else empty
string
R/C

Table of Contents