CHAPTER 3: IEC 61850 COMMUNICATION MODEL IMPLEMENTATION CONFORMANCE STATEMENT (MICS)
UR FAMILY – COMMUNICATIONS GUIDE 3-141
3
3.5.3.24 Thermal overload (ThmOvl)
This element is instantiated in the following products: B30, C60, C70, D30, D60, F35, F60, G30, G60, L30, L60, L90, N60, T35,
T60.
Table 3-162: Thermal overload data objects
3.5.3.25 Three pole autoreclose (Rec3p)
This element is instantiated in the following products: D30, F35, F60, L30.
Table 3-163: Three pole autoreclose data objects
units.SIUnit ENUMERATED 9 R
units.multiplier ENUMERATED 0 R
db INT32U CF SynChkRSYN#.ProjDifDis.db R/W/C
zeroDb INT32U CF 0 R
BlkRef1 ORG SYNCHK# BLOCK setting. R
GEORG R
setSrcRef ObjectReference SP SYNCHK# BLOCK. reference to the data attribute to input R/C
VISIBLE
STRING255
SP Reference to the ultimate source
of value selected by setting
SYNCHK# BLOCK.
R/C
setSrcCB ObjectReference SP source GoCB of input if via GOOSE R/C
VISIBLE
STRING255
SP If reference is external to this
IED, mapped to the source’s
GOOSE control block, else empty
string
R/C
cdcNs VISIBLE
STRING255
EX Name of the GE Multilin
namespace at the time of this
firmware release
R
cdcName VISIBLE
STRING255
EX GEORG R
InRef3 ORG SYNCHK# SYNC CLOSE setting. R
setSrcRef ObjectReference SP SYNCHK# SYNC CLOSE. reference to the data attribute to input R/C
R
setSrcCB ObjectReference SP source GoCB of input if via GOOSE R/C
R
LNName: ThmOvlPTTR# LDevice inst: Ctrl UR element: THERMAL OVERLOAD PROTECTION # element
data obj. data attribute Type FC UR Name Description R/W/C
Op ACT THERMAL PROT # OP operand R
general BOOLEAN ST THERMAL PROT # OP R
Str ACD THERMAL PROT # PKP operand R
general BOOLEAN ST THERMAL PROT # PKP R
dirGeneral ENUMERATED ST 0, the code for unknown. R
InRef2 ORG THERMAL PROT # RESET setting. R
setSrcRef ObjectReference SP THERMAL PROT # RESET reference to the data attribute to input R/C
setSrcCB ObjectReference SP source GoCB of input if via GOOSE R/C
BlkRef1 ORG THERMAL PROT # BLOCK setting. R
setSrcRef ObjectReference SP THERMAL PROT # BLOCK. reference to the data attribute to input R/C
setSrcCB ObjectReference SP source GoCB of input if via GOOSE R/C
LNName: Rec3pRREC# LDevice inst: Ctrl UR element: Autoreclose element # functions
data obj. data attribute Type FC UR Name Description R/W/C
ShotCnt INS AUTORECLOSE# SHOT COUNT actual
value
R
stVal INT32 ST AUTORECLOSE# SHOT COUNT R
AutoRecSt ENS Autoreclosing status R
LNName: SynChkRSYN# LDevice inst: Ctrl UR element: Synchrocheck element # (ANSI 25)
data obj. data attribute Type FC UR Name Description R/W/C