CHAPTER 5: IEC 60870-5-103 COMMUNICATION INTEROPERABILITY DOCUMENT
UR FAMILY – COMMUNICATIONS GUIDE 5-5
5
    <148>   Measurands I
L123
, V
L123
, P, Q, f
Generic functions in monitor direction
  INF   Semantics
 
   <240>   Read headings of all defined groups
 
   <241>   Read values or attributes of all entries of one group
 
   <243>   Read directory of a single entry
 
   <244>   Read value or attribute of a single entry
 
   <245>   End of general interrogation of generic data
 
   <249>   Write entry with confirmation
 
   <250>   Write entry with execution
 
   <251>   Write entry aborted
Selection of standard information numbers in control direction
System functions in control direction
   INF   Semantics
 
  <0>   Initiation of general interrogation
 
  <0>   Time synchronization
General commands in control direction
      INF   Semantics
 
   <16>   Auto-recloser on/off
 
   <17>   Teleprotection on/off
 
   <18>   Protection on/off
 
   <19>   LED reset
 
   <23>   Activate characteristic 1
 
   <24>   Activate characteristic 2
 
   <25>   Activate characteristic 3
 
   <26>   Activate characteristic 4
Generic functions in control direction
    INF   Semantics
 
   <240>   Read headings of all defined groups
 
   <241>   Read values or attributes of all entries of one group
 
   <243>   Read directory of a single entry
 
   <244>   Read value or attribute of a single entry
 
   <245>   General interrogation of generic data
 
   <248>   Write entry
 
   <249>   Write entry with confirmation
 
   <250>   Write entry with execution
 
   <251>   Write entry abort
Basic application functions
 
 Test mode
 
 Blocking of monitor direction
 
 Disturbance data
 
 Generic services
 
 Private data
Miscellaneous
Measurand max Mval = times rated value
1,2 or 2,4
Current L
1