2-64 UR FAMILY – COMMUNICATIONS GUIDE
MEMORY MAP CHAPTER 2: MODBUS COMMUNICATION
2
" 4388 ...Repeated for Route 5
" 438E ...Repeated for Route 6
Installation (Read/Write Setting)
All 43E0 Relay Programmed State 0 to 1 --- 1 F133 0 (Not
Programme
d)
" 43E1 Relay Name --- --- --- F202 “Relay-1”
User Programmable Self Tests (Read/Write Setting)
All 4441 User Programmable Detect Ring Break
Function
0 to 1 --- 1 F102 1 (Enabled)
" 4442 User Programmable Direct Device Off
Function
0 to 1 --- 1 F102 1 (Enabled)
" 4443 User Programmable RxGOOSE Off Function 0 to 1 --- 1 F102 1 (Enabled)
" 4444 User Programmable First Ethernet Fail
Function
0 to 1 --- 1 F102 0 (Disabled)
" 4445 User Programmable Second Ethernet Fail
Function
0 to 1 --- 1 F102 0 (Disabled)
" 4446 User Programmable Battery Fail Function 0 to 1 --- 1 F102 1 (Enabled)
" 4447 User Programmable SNTP Fail Function 0 to 1 --- 1 F102 1 (Enabled)
" 4448 User Programmable IRIG-B Fail Function 0 to 1 --- 1 F102 1 (Enabled)
" 444A Process Bus Failure Operand 0 to 4294967295 --- 1 F300 0
" 444C PTP Fail Function 0 to 1 --- 1 F102 1 (Enabled)
" 444D User Programmable Third Ethernet Fail
Function
0 to 1 --- 1 F102 0 (Disabled)
" 444E User Programmable SFP Fail Function 0 to 1 --- 1 F102 0 (Disabled)
(Current) CT Settings (Read/Write Setting) (6 Modules)
All except B90,
C30
4480 Phase CT 1 Primary 1 to 65000 A 1 F001 1
" 4481 Phase CT 1 Secondary 0 to 1 --- 1 F123 0 (1 A)
" 4482 Ground CT 1 Primary 1 to 65000 A 1 F001 1
" 4483 Ground CT 1 Secondary 0 to 1 --- 1 F123 0 (1 A)
" 4484 ...Repeated for CT Bank 2
" 4488 ...Repeated for CT Bank 3
" 448C ...Repeated for CT Bank 4
" 4490 ...Repeated for CT Bank 5
" 4494 ...Repeated for CT Bank 6
VT Settings (Read/Write Setting) (6 Modules)
All except B90,
C30
4500 Phase VT 1 Connection 0 to 1 --- 1 F100 0 (Wye)
" 4501 Phase VT 1 Secondary 25 to 240 V 0.1 F001 664
" 4502 Phase VT 1 Ratio 1 to 24000 :1 1 F060 1
" 4504 Auxiliary VT 1 Connection 0 to 6 --- 1 F166 1 (Vag)
" 4505 Auxiliary VT 1 Secondary 25 to 240 V 0.1 F001 664
" 4506 Auxiliary VT 1 Ratio 1 to 24000 :1 1 F060 1
" 4508 ...Repeated for VT Bank 2
" 4510 ...Repeated for VT Bank 3
" 4518 ...Repeated for VT Bank 4
" 4520 ...Repeated for VT Bank 5
" 4528 ...Repeated for VT Bank 6
Products Address Register name Range Units Step Format Default