GE Power Systems
D20 ME
Quick Start Guide
Code Download – D20 ME - CCU, Continued
Procedure: D20 ME - CCU (continued)
Step Action
Optional Step 2: To receive feedback during download
8 Configure the HyperTerminal to communicate at the same speed,
and reconnect to the 68K Monitor.
9 If the communication software you are using does not have a
“progress indicator’, you can enable echo to visually display the
code file on the monitor during transfer.
The echo option can be usually found in the Communication
Settings or Properties of the communication program.
Note: Enabling echo may slow the transfer speed.
Download Code File
10 Type dl and press ENTER to ready the D20 ME to receive the
downloadable code file.
11 Click Transfer | Send Text File from menu bar
Result: A dialog box opens, prompting you to locate the
Down.shx file that you wish to download.
12 Select the correct file, and click Open to start the transfer.
Result: The file transfer may take from less than 10 minutes to
over 40 minutes, depending on the communication speed
selected.
When complete, the D20M> prompt returns.
13 Type el /p to display the error log.
Result: The D20ME> prompt should return, indicating no errors
found.
Errors? Record error(s), and re-try download.
If errors persist, contact GE for support.
14 Type el /r to ensure that log is clear, then type Boot to restart.
Result: The D20 ME code download is complete.
994-0025-1.00-8 General
12
Full Release