DGP Digital Generator Protection System GE Power Management
2.4 COMMISSIONING 2 CALCULATION OF SETTINGS
2
CURRENT UNBALANCE – TRIP: 46T
401 TRIP Configure trip outputs
402 ALARM Configure alarm outputs
403 PICKUP Pickup current (Negative sequence) Amps
404 K2 K factor Sec.
LOSS OF EXCITATION – SUPERVISION: 40
501 SELV2SUP Select V2 supervision of 40
LOSS OF EXCITATION – ZONE 1: 40-1
601 TRIP Configure trip outputs
602 ALARM Configure alarm outputs
603 CENTER Center of characteristic Ohms
604 RADIUS Radius of characteristic Ohms
605 TL12 Timer TL12 setting Sec.
LOSS OF EXCITATION – ZONE 2: 40-2
701 TRIP Configure trip outputs
702 ALARM Configure alarm outputs
703 CENTER Center of characteristic Ohms
704 RADIUS Radius of characteristic Ohms
705 TL13 Timer TL13 setting Sec.
ANTI-MOTORING #1: 32-1
801 TRIP Configure trip outputs
802 ALARM Configure alarm outputs
803 SQ TR EN Enable sequential trip
804 REV PWR Reverse power pickup Watts
805 TL1 Timer TL1 setting Sec.
ANTI-MOTORING #2: 32-2
901 TRIP Configure trip outputs
902 ALARM Configure alarm outputs
903 REV PWR Reverse power pickup Watts
904 TL2 Timer TL2 setting Sec.
Table 2–7: DGP
***
ACA SETTINGS TABLE (Sheet 2 of 6)
LOCATION: GENERATOR NUMBER:
RELAY MODEL NUMBER: DGP _ _ _ ACA PROM VERSION NUMBER: V _ _ _ . _ _ _ _ _ D
SETTING # MNEMONIC DESCRIPTION USER SETTING