EasyManua.ls Logo

GE KL700 - Page 16

GE KL700
16 pages
Print Icon
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
16 KL700 series installation manual (55370072)
KL700 KL710 KL731
Certification
Certification body 1175 1175 1175
Certificate year 07 07 07
Certificate number 1175-CPD-011 1175-CPD-007 1175-CPD-009
Compliance EN54-7 EN54-5 EN54-7
Class - A2 -
Supply voltage 18 – 28 VDC 18 – 28 VDC 9 – 28 VDC
Standby current 30 µA 70 µA 85 µA
Alarm current < 100 mA < 100 mA < 100 mA
Operating temperature -10 to 60 °C -10 to 70 °C -10 to 70 °C
Storage temperature -10 to 70 °C -10 to 80 °C -10 to 70 °C
Maximum relative humidity 95% 95% 95%
Dimensions 45 x Ø 99 mm 45 x Ø 99 mm 45 x Ø 99 mm
Maximum number of detectors per
zone
20 20 20
EMC standards EN 50130-4, EN 50081-2 EN 50130-4, EN 50081-2 EN 50130-4, EN 50081-2
Protection index IP42 IP42 IP42
Product variant - - KL731B
Base KZ700 KZ700 KZ700
Kilsen S.L.U. acting under the name of GE Security
Verge de Guadalupe 3
08950, Esplugues de Llobregat
Barcelona, Spain