GE DE LanPro-11U UPS: Installation / User Manual 2.1 (US)
GE Digital Energy
g
• Use insulated copper input and output wiring, rated 90°C derated to 40°C wire size based on the ampacities
given in Tables 310-16 of the National Electrical code, ANSI/NFPA 70-1993.
This wiring shall have the following minimum sizes:
INPUT WIRING:
Utility voltage
UPS model 120V 208V 240V
L5-11U 6 AWG 10 AWG 10 AWG
L6-11U 4 AWG 8 AWG 10 AWG
L8-11U N/A 6 AWG 8 AWG
L10-11U N/A 4 AWG 6 AWG
Table 2. Input wiring
OUTPUT WIRING:
Output voltage
UPS model 120V 208V 240V
L5-11U 8 AWG 10 AWG 10 AWG
L6-11U 8 AWG 10 AWG 10 AWG
L8-11U 6 AWG 8 AWG 8 AWG
L10-11U 4 AWG 8 AWG 8 AWG
Table 3. Output wiring
TIGHTENING TORQUE FORCE:
UPS model Tightening torque force
L5/6-11U/120V 22 Lbs/inch
All other models 18-20 Lbs/inch
Table 4. Tightening torque force