EasyManua.ls Logo

GE Power Break II - Power Break II Circuit Breakers; Advanced Solid-State Trip Units

GE Power Break II
4 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Horizontal
Interconnection
3
.
For
a
horizontal
installation
,
attach
the
long
rod
ends
to
the
pins
on
the
pivots
as
shown
in
Fig
-
ure
9
.
A
variety
of
connecting
hardware
is
pro
-
vided
in
the
Mechanical
Interlock
kit
;
the
i
/
4
-
20
threaded
rod
is
supplied
by
the
customer
.
4
.
Slip
the
provided
heat
-
shrink
tubing
over
the
rod
so
that
it
provides
insulation
within
the
compartment
through
which
the
rod
passes
(
right
-
side
unit
)
.
Shrink
the
tubing
in
place
with
a
hot
air
source
of
100
300
°
C
(
212
572
°
F
)
.
5
.
Adjust
the
length
of
the
rod
so
that
the
pivot
-
to
-
pivot
distance
is
equal
to
the
center
-
to
-
center
dis
-
tance
between
the
two
compartments
.
Figure
7
.
Installation
of
a
compartment
unit
onto
the
breaker
mounting
support
.
Rod
Extender
tion
)
,
the
type
A
unit
must
be
installed
in
the
upper
compartment
and
the
type
B
in
the
lower
.
If
the
breakers
are
mounted
side
by
side
(
horizontal
connection
)
,
the
type
A
unit
must
be
installed
in
the
right
compartment
and
the
type
B
in
the
left
.
C
-
Rod
Connector
"
B
"
Unit
Attach
to
Lower
Long
Rod
End
Pivot
Point
on
Vertical
Interconnection
3
.
For
a
vertical
installation
,
attach
the
rod
ends
to
the
pivots
as
shown
in
Figure
8
.
The
rod
ends
are
provided
in
the
Mechanical
Interlock
kit
;
the
i
/
4
-
20
threaded
rod
is
supplied
by
the
cus
-
tomer
.
4
.
Adjust
the
length
of
the
rod
so
that
the
pivot
-
to
-
pivot
distance
is
equal
to
the
distance
between
the
two
compartments
.
Both
Units
Lock
Nut
Figure
9
.
Attachment
of
the
interconnection
rod
to
the
compartment
units
for
a
horizontal
installation
..
The
view
is
from
the
rear
of
the
compartment
Lower
Link
Installation
Testing
1
/
,
"
A
"
Unit
Before
installing
the
breakers
,
verify
that
the
rod
linkage
is
centered
and
free
to
move
in
either
direc
-
tion
.
After
installing
the
breakers
in
the
compartments
,
charge
the
closing
springs
on
both
breakers
.
Close
one
of
the
breakers
,
then
attempt
to
close
the
other
.
The
second
breaker
should
immediately
trip
.
Repeat
the
test
with
the
breakers
in
the
opposite
order
.
If
the
sec
-
ond
breaker
does
not
trip
in
either
case
,
check
that
the
rod
connecting
the
breakers
is
free
to
move
i
n
both
directions
when
the
breakers
are
sequenced
from
OFF
to
ON
.
If
the
rod
is
adjusted
too
short
,
one
of
the
breakers
will
nuisance
trip
even
when
the
other
breaker
is
off
.
If
the
rod
is
adjusted
too
long
,
the
inter
-
lock
mechanism
will
not
operate
properly
.
A
good
length
is
one
that
eliminates
the
slack
between
the
compartment
linkages
.
Washer
and
Cotter
Pin
Lock
Nut
Rod
End
Jpper
Link
Figure
8
Attachment
of
the
interconnection
rod
to
the
compartment
units
for
a
vertical
installation
.
The
view
is
from
the
rear
of
the
compartment
.
Courtesy of NationalSwitchgear.com

Other manuals for GE Power Break II

Related product manuals