GRASSO SYSTEM CONTROL
Kap.9 - 6 638660E_chapter9.doc 01.2003/ 0
# Title Unit HotKey
50 Configuration DIR Parameters for configuration values
Range Default setting Project setting
Sensor scaling:
Intermediate temperature
HP
Sensor: Intm temp HP
Offset (K) °C -10,0 ... 10,0 0,0
Spann (%) °C -20,0 ... 20,0 0,0
Sensor scaling:
Oil temperature
Sensor: Oil temp
Offset (K) °C -10,0 ... 10,0 0,0
Spann (%) °C -20,0 ... 20,0 0,0
Sensor scaling:
Motor current
Sensor: Motor current
Begin (4mA) A 0,0 ... 1500,0 0,0
End (20mA) A 0,0 ... 1500,0 600,0
Sensor scaling:
Motor speed
Sensor: Motor speed
Begin (4mA) rpm 0,0 ... 3000,0 0,0
End (20mA) rpm 0,0 ... 3000,0 2000,0
Sensor scaling:
Frequency output
Sensor: Frequency out
Begin (4mA) rpm 0,0 ... 3000,0 0,0
End (20mA) rpm 0,0 ... 3000,0 2000,0
Sensor scaling:
Capacity output
Sensor: Capacity out
Begin (4mA) % 0,0 ... 100,0 0,0
End (20mA) % 0,0 ... 100,0 100,0
Sensor scaling:
Oil separator temperature
Sensor: Separat temp
Offset (K) °C -10,0 ... 10,0 0,0
Spann (%) °C -20,0 ... 20,0 0,0