GRASSO SYSTEM CONTROL
Chap. 2 - 12 638660E_chapter2.doc 01.2004/1
2.7.1.2 Switching sequence in case of too low oil differential pressure alarm during running
Output — compressor motor on
’Oil dif press’ OK
’Oil dif run’ timer active
’Low oil differential pressure’ alarm
Figure 2.14, Oil system monitor in case of too low oil
differential pressure alarm during running
If
(1) Output — compressor motor on equals 1
and
If
(2) ’Oil dif press’ OK equals 0
Then
(3) Start ’Oil dif run’ timer
If
(3) ’Oil dif run’ timer expired
and
If
(2) ’Oil dif press’ OK equals 0
Then
(4) ’Low oil differential pressure’ alarm