GRASSO SYSTEM CONTROL
Chap. 3 - 6 638660E_chapter3.doc 01.2003/0
3.5 Adjusting limit values
Press ,
Select the main menu 20 “Limit values“. The following selection appears on the display:
Suction press 
Psuc low alarm 
Low warning + 
Limit values 01 >>
Page on using the key.
Adjust the limit values to the suit the refrigeration plant.
3.6 Adjusting time values
Press ,
Select the main menu 30 “Timer values“. The following selection appears on the display:
Start to start 
Stop to start 
Timer values 01 >>
Page on using the key.
Adjust the timer values to the suit the refrigeration plant.
3.7 Parameterise unit options
Press ,
Select the main menu 35 “Unit options“. The following selection appears on the display:
Unit options
Sequence control
Act val Parameter
I I >>
Use the key “Parameter” to select the sequence control parameter list.
Use the key “Act val” to select the actual values of the master and slave.
Press once. The following selection appears on the display:
Unit options
Economiser
Act val Parameter
<< I I
Use the key “Parameter” to select the economiser parameter list.
Use the key “Act val” to select the actual economiser values.