1. Choose the entry
- Devices
- UPS
- Events
from the drop-down menu.
2. Click the Button “+” next to the event “Powerfail”.
3. The Job-Editor starts. Choose the option
RCCMD Shutdown” from the menu.
4. Enter the „IP Address“ of your client (The
Listener Port is usually 6003). At the right side you
can
specify when the shutdown signal is going to be
released, for example „At 300 seconds remaining
time“.
5. Click the button „Save Configuration“.
6. For security reasons it is recommended to make
the same RCCMD shutdown entries at „Powerfail“ for
the Event “Battery low” - but here without any delays
to avoid that the server crashes because of low
battery alarm!
The CS141 can be a variety of environmental
sensors and other measuring devices are combined,
to temperature, humidity, fire and smoke, motion and
intrusion, pressure, levels etc. to be monitored.
In addition, other components such as various
mounting brackets, BACnet Converter, PROFIBUS
Converter etc. available. Please ask your UPS
manufacturers / suppliers for more detailed
information about the options available.