Exporting UPS data log
If needed for later analysis for statistical and diagnostic purposes, the CS141 provides to export and save
the log as CSV file and save it locally to your hard disk
Note:
The UPS Event Recorder polls the current list from the UPS with each call - These log data will not be cached or saved by CS141.
Tools
The GENEREX system tools are a collection of useful utilities to help in case of diagnostic problems. To ensure authorized access only,
this menu acquire administrative credentials:
To open the Toolbox, navigate to the following menu:
Reboot
Due to the fact the CS141 accept changes inside the configuration and start or restarts the
corresponding system services in real time, a complete restart is an exceptional situation. In case of
a restart of the CS141, UPS continues its normal mode: A reboot of CS141 does not affect the UPS.
To prevent an accidental triggered reboot, this feature was deliberately placed inside Tools.
Tracer
The Tracer is a comprehensive diagnostic tool for verifying communication
between the CS141 and the connected devices as well as for identifying
network problems.
Under Device communication information about external devices connected
to CS141 can be queried. To track a device, open the context menu and
select the device you want to monitor. As the screenshot illustrates, the CS141 provides COM 1 / UPS, COM 2 / GSMModem and COM
3 / AUX-Port:
COM 1/ UPS
The tracer will screen the current communication running at the serial RS232 port. Faults or faulty communication are displayed in real
time and can be saved for later evaluation
COM 2 / GSM-Modem
The Tracer queries the communication between the CS141 and the GSM modem and displays the telemetry in real time. Errors and
communication problems can be easily collected and saved for later analysis.
COM 3 / AUX
A CON_AUX4 or CON_R_AUX4 can be connected via the AUX port. The tracer can interrogate communication with the device in real
time.
Note:
The Tracer adapts itself to the choice met under Devices in the configured in general port
settings. If sensors or a Sensor manager 2 is configured instead of a GSM modem, the tracer
will show these devices.