The module will be triggered by the BACS webmanager to fall back to normal operation.
BACS programmer Single mode
The single mode is an option to progam one single BACS module or
change module ID’s inside an existing BACS installation.
Please note for this function it is mandatory to know the exact ID of the
according module you wish to prorgam.
If you are unsure about the current ID, please reset the module to
factory defaul ID 0. If you know the module’s ID, you may sklp resetting
the module and use the current ID.
At „Old“, enter the current module ID. With „New“,the new module ID
can be entered. Set will start the programming procedure. By doing so, it is not required to push the confirmation button at the BACS
module.
The BACSmodule will confirm the setting by flashing slowly green.
Using single mode inside a BACS installation
This function can be used to change module ID’s inside an existing BACS installation – this will allow to resort BACS-Modules according
to the physical wiring. The according module can be logically set to a string it is physicalle installed. Please note: You can program two
modules with the same address. As a consequence, BACS will not start because of an address conflict. if you set up two modules with
the same address, you need to seperate the ID’s with a hard reset of one of these modules or by disconnecting on module. Otherwise
these modules will receive and confirm the new ID simultanously.
Checking ID programming:
If unsure, it is mandatory to check the ID’s of the modules. With this tool you can check …
- If the module responds to the intended ID
- If there are two modules with the same ID inside a BACS installation.
Search a BACS module
Under Module, enter the ID you want to find and press show:
All modules will start blinking green, with one extention:
The module with the entered ID will blink red/green.
The blinking will stop by pressing the confirmation button oft he
module or at the BACS programmer pop up confirmation dialog.
If you set up an ID twice, both modules will start blinking this way.
If BACS cannot find the module, it will display an according message.