You do not necessarily have to decouple the entire BACS system if you want to specifically check a specific section within a large
system - but you need to ensure only one BACS Bus Converter will access the tested modules:
In this example, a cable was taken from the BACS 1 and connected via a BACS bus converter to the COM port of the laptop.
In this constellation, both BACS bus converters would disturb each other until the segment to be tested is completely decoupled and
separated:
The number as well as the module ID's of BACS modules that can be tested is determined by the technician who interrupts the data
connection.
Note
WIf you are looking for a fault in the cabling, you should check with both, a simple and a ring cabling. If several modules are affected in
the middle, you can determine the source of the error exactly from both sides. This allow you to find the affected section. However, if
there is only one cable faulty, you will need the simple wiring to locate the faulty cable or module.