When finished with configuration, open the GX_R_AUX configuration dialog
Your settings changed thee entries and fixed them to a special functionality:
All you need to do is the definition whether the battery breaker you are using are Normally Open (NO) Contacts or Normally Closed
(NC) contacts. Due to the fact, both concepts are in use, BACS cannot know which type of battery breakers are currently in use.
Open BACS event handling and search for BACS thermal Runaway String 1, 2 und 3 and unfold them:
The BACS Webmanager automatically added an AUX-Job to switch the battery breaker.
Press the test button to check whether the battery breaker will be triggered and opens accordingly. If not, you need to configure the
NC/NO-Contacts of the BACS GXR_AUX to the correct position and check wiring at the device itself.
Note
If you configure the Thermal Runaway after configuring GX_R_AUX outputs, be sure to check for previously entered events for
plausibility:
You may also need to open the battery interrupters for other reasons, the Thermal Runaway configuration dialog will only work on a
specific scenario and configuration routine automatically:
The outputs are renamed and a preconfigured job is automatically added to the corresponding events. Since the BACS Web Manager
cannot know why you entered these additional conditions, BACS will not remove all your configurations automatically-
It is up to you to check them manually.