RCCMD is a client that will always wait for an incoming signal! You need to configure an RCCMD sender like the CS141 Web
manager:
At UPS event management, select as job RCCMD Shutdown you may choose between the IP address or the host name of the
RCCMD client.
In critical resource management, it is advisable to eliminate as many interfering possibilities as possible.
As an example, if you need a server that can resolve the hostnames into IP addresses, the communication between client and
sender will stop working as soon as the server is unavailable.
Therefore, the general recommendation is to use a manual IP addresses: by doing so, all devices inside a network segment can
communicate with each other without additional server.
Note
If you configure the CS141 and want to see if the jobs you have configured are correctly received by RCCMD, you can use
connections to create an inbound log. As long as the sender is not explicitly included in Connections, RCCMD will log the
execution but refuse to execute it.
However, at least one IP address must be entered in order to activate this filter function.
Preparing UPS redundancy
Some settings depend on each other. If you have several UPS systems paired in operation in order to secure the server
infrastructure, it may be necessary to specify more than one UPS to trigger a shut down command.
If you enter two or more valid IP addresses for a valid RCCMD signal, the "Redundancy" menu is automatically activated and
can be used.
RCCMD can be configured to manage valid RCCMD shutdown signals from different sources. For details, refer to the menu
"Redundancy".
How to delete an IP address
Click on the IP address and press Remove.
This will delete the IP address.
Remember to press Save changes at the upper right position to save
your settings permanently.