As soon as the second system instructs a shutdown, this command is executed and the system shuts down. If a shutdown
signal is sent by the first system and the second system is not reachable, RCCMD shuts down the system - in this case,
RCCMD assumes that the second system is not available.
Shutdown behavior with three valid devices
From three devices onwards, the redundancy behavior can be individually adjusted to necessary conditions:
1. If one of three systems send a shutdown
2. When two out of three systems send a shutdown
3. All three systems must decide the shutdown together.
Each system can individually instruct and withdraw its shutdown via the RCCMD Custom command wakeup. In general,
RCCMD will not execute the shutdown until the exact shutdown condition is met.
Redundancy-related scripting
If you use redundancy behavior, the RCCMD client waits to execute the shutdown until the appropriate number of devices also
instruct the shutdown.
Because this process has a direct impact on the operation of
the servers being monitored by RCCMD, a script will be
launched to indicate an incident.
Use Edit File ... to customize and adapt this script to your
individual requirements.
Abort will close the editor and withdraw all changes you
made.
As a default, a text notification is pre-defined to indicate a
redundancy-based shutdown behavior.