77
113
U
3/4
Alarm: Overtemperature
1 = active; 0 = not active
1
114
U
3/4
Alarm: Input Bad
1 = active; 0 = not active
1
115
U
3/4
Alarm: Output Bad
1 = active; 0 = not active
1
116
U
3/4
Alarm: Output Overload
1 = active; 0 = not active
1
117
U
3/4
Alarm: On Bypass
1 = active; 0 = not active
1
118
U
3/4
Alarm: Bypass Bad
1 = active; 0 = not active
1
119
U
3/4
Alarm: Ouput Off As Requested
1 = active; 0 = not active
1
120
U
3/4
Alarm: UPS Off As Requested
1 = active; 0 = not active
1
121
U
3/4
Alarm: Charger Failed
1 = active; 0 = not active
1
122
U
3/4
Alarm: UPS Output Off
1 = active; 0 = not active
1
123
U
3/4
Alarm: UPS System Off
1 = active; 0 = not active
1
124
U
3/4
Alarm: Fan Failure
1 = active; 0 = not active
1
125
U
3/4
Alarm: Fuse Failure
1 = active; 0 = not active
1
126
U
3/4
Alarm: General Fault
1 = active; 0 = not active
1
127
U
3/4
Alarm: Diagnosis Test Failed
1 = active; 0 = not active
1
128
U
3/4
Alarm: Communication Lost
1 = active; 0 = not active
1
129
U
3/4
Alarm: Awaiting Power
1 = active; 0 = not active
1
130
U
3/4
Alarm: Shutdown Pending
1 = active; 0 = not active
1
131
U
3/4
Alarm: Shutdown Imminent
1 = active; 0 = not active
1
132
U
3/4
Alarm: Test In Progress
1 = active ; 0 = not active
1
133
U
3/4
AUX Port 1
1 = active (high) ; 0 = not active (low)
1
134
U
3/4
AUX Port 2
1 = active (high) ; 0 = not active (low)
1
135
U
3/4
AUX Port 3
1 = active (high) ; 0 = not active (low)
1
136
U
3/4
AUX Port 4
1 = active (high) ; 0 = not active (low)
1
137
U
3/4
SensorManager/SMTH_COM,
Sensor 1
Analog Value
1
138
U
3/4
SensorManager/SMTH_COM,
Sensor 2
Analog Value
1
139
U
3/4
SensorManager/Sensor 3
Analog Value
1
140
U
3/4
SensorManager/Sensor 4
Analog Value
1
141
U
3/4
SensorManager/Sensor 5
Analog Value
1
142
U
3/4
SensorManager/Sensor 6
Analog Value
1
143
U
3/4
SensorManager/Sensor 7
Analog Value
1
144
U
3/4
SensorManager/Sensor 8
Analog Value
1
145
U
3/4
Result of the last Battery Test
Value 3 = Battery Test passed, Value 4 =
Battery Test failed
1
Section OEM: Netminder EON