Other OEM’s : See OEM MODBUS Defaultadress 100 – 146 above
UPSMAN Status Bytes - Standard Device Status Bits
Example (decimal):
STATUS= „5” means UPS_SB_OUTPUT_ACT (4) + UPS_SB_BYPASS_MODE (1) are active ! = UPS on Bypass!
STATUS= „12” means UPS_SB_OUTPUT_ACT (4) + UPS_SB_BACKUP_MODE (8) are active ! = UPS Powerfail!
STATUS= „28” means UPS_SB_OUTPUT_ACT (4) + UPS_SB_BACKUP_MODE (8) + UPS_SB_BATTERY_LOW (16) are
active ! = UPS Powerfail and Battery low!
STATUS= „4” means UPS_SB_OUTPUT_ACT (4) + no other alarms = UPS OK