EasyManua.ls Logo

Generex CS141 - Page 309

Generex CS141
320 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
v.: 2020-09-04
Copyright of the European Union is effective (Copyright EU) (c) 2019 GENEREX Systems GmbH, Hamburg, Germany, All rights reserved
TEL +49(40)22692910 - EMAIL generex@generex.de - WEB www.generex.de (This and all other product datasheets are available for download.)
106
BACS_STATE_NONE 0x0000 0
BACS_STATE_RUNNING 0x0001 1
BACS_STATE_CONNECTED 0x0002 2
BACS_ STATE_MODULE_LOST 0x0004 4
BACS_STATE_DISCHARGING 0x0008 8
BACS_STATE_CHARGING 0x0010 16
BACS_STATE_DISCHARGING_STOPPED 0x0020 32
BACS_STATE_FLOAT_CHARGING 0x0040 64
BACS_STATE_EQUALISATION 0x0080 128
BACS_STATE_SYSTEM_FAILURE 0x0100 256
BACS_STATE_VOLTAGE_OUTOFRANGE 0x0200 512
BACS_STATE_TEMPERATURE_OUTOFRANGE 0x0400 1024
BACS_STATE_RESISTOR-OUTOFRANGE 0x0800 2048
BACS_STATE_MODULE-ADDRESSING 0x1000 4096
BACS_STATE_MODULE-SEARCHING 0x2000 8192
BACS_STATE_MODULE-INITIALIZING 0x4000 16384
BACS_STATE_MODULE-POLLING 0x8000 32768
*5 Address 1001 MODBUS/SNMP (hexadecimal) (decimal)
BACS_STATE-GENERAL-ALARM 0x0001 1
BACS_STATE-VOLTAGE-DIFF-HIGH 0x0002 2
BACS_STATE-BATTERY-BREAKER-OPEN 0x0004 4
BACS_STATE_THERMAL_RUNAWAY 0x0008 8
*6 Address 1002 Alarm Flags MODBUS/SNMP (hexadecimal) (decimal)
BACS_ALARM_NONE 0x0000 0
BACS_ALARM_GENERAL_ALARM 0x0001 1
BACS_ALARM_COMMUNICATION_LOST 0x0002 2
CS_ALARM_VOLTAGE_HIGH 0x0004 4