When it is active, low oil pressure stop is inhibited.
In Auto mode, when input active, gen-set can start and take load after
gen-set is OK; when input inactive, gen-set will stop automatically.
Connected to sensor’s digital input. The controller sends a warning alarm
signal when it is active.
Low Coolant Level
Warning
Connected to sensor digital input. The controller sends a shutdown alarm
signal when active.
Low Coolant Level
Shutdown
In Auto Mode, when the input is active, no matter mains normal or not,
gen-set won’t start. If gen-set is in normal running, stop process won’t be
executed. When input is disabled, gen-set will automatically start or stop
judging by mains normal or not.
All buttons in panel is inactive and Remote Mode is displayed on LCD.
Remote module can switch module mode and start/ stop operation via panel
buttons.
Connect to failed to charge output.
All keys in panel are inactive except set-keys and there is in the first
row of the front page in LCD when input is active.
This input can prohibit “Audible Alarm” output when input is active.
In this mode, under voltage, under frequency and under speed are not
protected.
When input is active, controller will initiate fuel leakage alarm.
If engine type is common J1939 engine target speed will increase 5RPM.
If engine type is common J1939 engine target speed will decrease 5RPM.
In case of over current, controller will initiate shutdown alarm.
In case of over speed, controller will initiate shutdown alarm.