When the oil pressure sensor value is under this point, Low
Oil Pressure alarm is sending out. When the value is “0”,
warning alarm won’t be sent. (This function is only suited
for oil pressure sensor, except for low oil pressure alarm
signal inputted by programmable input port.)
When fuel level sensor value is under this point and
remains for 10s, genset sends out warning alarm. This
function is only warning but not shutdown.
If the liquid level of the external liquid level sensor is
lower than this value and lasts for 5 seconds, the shutdown
signal will be sent.
When the delay setting as “0”s, this function is only
warning but not shutdown.
During genset normal running, when B+ and charger D+
(WL) voltage difference is above this value for 5s, the
controller issues “Charging Failure” warning.
When generator battery voltage is over this value and
remains for 20s, battery over voltage signal is active. This
function is only warning but not shutdown.
When generator battery voltage is under this value and
remains for 20s, battery under voltage signal is active. This
function is only warning but not shutdown.
External current transformer ratio.
Rated current of generator, used for calculating over load
current.
According to the selected action, action for the power
generation over current 0: No Action, 1: Electrical Trip, 2:
Alarm Shutdown
When load current is over this value, the over current delay
is initiated.
This is delay time in case of over current.
When the fuel level lower than the set value for 2s, it sends
a signal to open fuel pump.
When the fuel level higher than the set value for 2s, it
sends a signal to close fuel pump.
Factory default: Energized to stop. See 7. Outputs Title.
Factory default: Idle control. See 7. Outputs Title.
Factory default: Gens closed. See 7. Outputs Title.