No
Parameter
Range
Default
Description
31(26)
Low Oil Pressure
(0-400)kPa
103
When the oil pressure sensor value is under this point, Low
Oil Pressure alarm is sending out. When the value is “0”,
warning alarm won’t be sent. (This function is only suited
for oil pressure sensor, except for low oil pressure alarm
signal inputted by programmable input port.)
32(27)
Low Fuel Level Warning
(0-100)%
10
When fuel level sensor value is under this point and
remains for 10s, genset sends out warning alarm. This
function is only warning but not shutdown.
33(28)
Low Fuel Level
Shutdown
(0-100)%
5
If the liquid level of the external liquid level sensor is
lower than this value and lasts for 5 seconds, the shutdown
signal will be sent.
34(29)
Speed Signal Loss Time
(0-20.0)s
5.0
When the delay setting as “0”s, this function is only
warning but not shutdown.
35(30)
Charge Fail Voltage
(0-30)V
6.0
During genset normal running, when B+ and charger D+
(WL) voltage difference is above this value for 5s, the
controller issues “Charging Failure” warning.
36(31)
Battery Over Voltage
(12.0-40.0)
V
33
When generator battery voltage is over this value and
remains for 20s, battery over voltage signal is active. This
function is only warning but not shutdown.
37(32)
Battery Under Voltage
(4.0-30.0)V
8
When generator battery voltage is under this value and
remains for 20s, battery under voltage signal is active. This
function is only warning but not shutdown.
38(33)
CT Ratio/5
(5-6000)/5
500
External current transformer ratio.
39(34)
Full Load Current
(5-6000)A
500
Rated current of generator, used for calculating over load
current.
40(35)
Over Current Action
0-2
2
According to the selected action, action for the power
generation over current 0: No Action, 1: Electrical Trip, 2:
Alarm Shutdown
41(36)
Over Current Percentage
(50-130)%
120
When load current is over this value, the over current delay
is initiated.
42(37)
Over Current Delay
(0-3600)s
30
This is delay time in case of over current.
43(38)
Fuel Pump On Value
(0-100)%
25
When the fuel level lower than the set value for 2s, it sends
a signal to open fuel pump.
44(39)
Fuel Pump Off Value
(0-100)%
80
When the fuel level higher than the set value for 2s, it
sends a signal to close fuel pump.
45(40)
Aux. Output 1 Function
(0-25)
2
Factory default: Energized to stop. See 7. Outputs Title.
46(41)
Aux. Output 2 Function
(0-25)
3
Factory default: Idle control. See 7. Outputs Title.
47(42)
Aux. Output 3 Function
(0-25)
5
Factory default: Gens closed. See 7. Outputs Title.