No
Parameter
Range
Default
Description
48(43)
Aux. Output 4 Function
(0-25)
6
Factory default: Mains closed. See 7. Outputs Title.
49(44)
Aux. Input 1 Function
(0-25)
1
Factory default: High temperature alarm input.
See 8. Inputs Title.
50(45)
Aux. Input 1 Valid
(0-1)
0
Factory default: Closed.
51(46)
Aux. Input 1 Delay
(0-20.0)s
2
Input signal active delay.
52(47)
Aux. Input 2 Function
(0-25)
2
Factory default: Low oil pressure alarm input. See 8. Inputs
Title.
53(48)
Aux. Input 2 Valid
(0-1)
0
Factory default: Closed.
54(49)
Aux. Input 2 Delay
(0-20.0)s
2
Input signal active delay.
55(50)
Aux. Input 3 Function
(0-25)
10
Factory default: Remote start input. See 8. Inputs Title.
56(51)
Aux. Input 3 Valid
(0-1)
0
Factory default: Closed.
57(52)
Aux. Input 3 Delay
(0-20.0)s
2
Input signal active delay.
58(53)
Aux. Input 4 Function
(0-25)
11
Factory default: Low fuel level alarm input.
See 8. Inputs Title.
59(54)
Aux. Input 4 Valid
(0-1)
0
Factory default: Closed.
60(55)
Aux. Input 4 Delay
(0-20.0)s
2
Input signal active delay.
61(56)
Aux. Input 5 Function
(0-25)
12
The factory default: low cooling liquid level alarm input.
See 8. Inputs Title.
62(57)
Aux. Input 5 Valid
(0-1)
0
Factory default: Closed.
63(58)
Aux. Input 5 Delay
(0-20.0)s
2
Input signal active delay.
64(59)
Power On Mode
(0-2)
0
0Stop; 1Manual; 2Auto (When the controller energized,
controller starts with this mode.)
65(60)
Controller Adress
(1-254)
1
Module communication address.
66(61)
Password Setting
(0-9999)
1921
All parameters can be set. See title 5.
67(62)
Disconnect Gens Speed
(0-3000)
r/ min
360
When engine speed reached this value, starter will
disconnect.
68(63)
Disconnect Gens
Frequency
(0.0-30.0)
Hz
14
When generator frequency reached this value, starter will
disconnect.
69(64)
Disconnect Gens Oil
Pressure
(0-400)kPa
200
When engine oil pressure is over this value, starter will
disconnect.