No
Parameter
Range
Default
Description
70(65)
High Temp. Stop
Inhibit
(0-1)
0
Default: When temperature is overheat, the genset alarms
and shutdown.
71(66)
Low OP Stop
Inhibit
(0-1)
0
Default: When oil pressure is too low, the genset alarms
and shutdown.
72(67)
AC system
(0-2)
0
0 3 Phase 4 Wire (3P4W)
1 2 Phase 3 Wire (2P3W)
2 1 Phase 2 Wire (1P2W)
73(68)
Temp. Sensor
Curve Type
(0-10)
8
SGX. See title 9.
74(69)
Pressure Sensor
Curve Type
(0-9)
8
SGX. See title 9.
75(70)
Level Sensor
Curve Type
(0-3)
3
SGX. See title 9.
76(71)
Generator Poles
(2-64)
4
Number of magnetic poles, used for calculating rotating
speed of generator without speed sensor.
77(72)
Temp. Sensor Open
Action
(0-2)
1
0: Disabled; 1: Warning; 2: Shutdown
78(73)
Oil Pressure Sensor
Open Action
(0-2)
1
0: Disabled; 1: Warning; 2: Shutdown
79(74)
Level Sensor Open
Action
(0-2)
1
0: Disabled; 1: Warning; 2: Shutdown
80(75)
Disconnect Oil
Pressure Time
(0-20.0)s
0
When disconnect conditions include oil pressure and
engine oil pressure is higher than disconnect oil pressure
delay, the genset is regarded as start successfully and starter
will disconnect.
81(76)
Over Power Setting
(0-2)
0
0: Disabled; 1: Warning; 2: Shutdown
When the power is greater than the set value and the
duration is greater than the delay value, the overpower
alarm is effective. The return value and delay value can
also be set.
82(77)
Welcome Page Setting
(0-1)
1
0: Disabled; 1: Enabled.
Start interface delay can be set.
83(78)
Maintenance
Password
(0-9999)
1234
Enter password interface of maintenance configuration.
84(78)
Date/ Time
Set the date/ time of controller.
85(79)
Fuel Output Time
(1-60)s
1
It is the time of the genset fuel output during power on.
86(80)
Manual Mod ATS
(0-1)
0
0: Key Switch; 1: Auto Switch.
87(81)
Speed Raise Pulse
(0-20.0)s
0.2
It is the speed-up pulse output time, when the unit begin the
high-speed warm-up.