It is the speed-drop pulse output time, when the unit begin
to idling for stop.
It is duration to open ATS.
0 User-defined temperature sensor,
1 User-defined pressure sensor,
2 User-defined level sensor,
Choose sensor which need to be set, input every point
resistance (or current/ voltage) and corresponding value of
curve, 8 points need to be entered.
00 Conventional Gen-set
01 Standard J1939
Used to calculate active power/ rated power percentage.
Conditions of disconnecting starter (generator, magnetic
pickup sensor, oil pressure), each condition can be used
alone and simultaneously to separating the starter-motor
and genset as soon as possible.
When the engine speed is over the value for 2s, alarm
signal is sent.
When the engine speed is under the value for 10s, alarm
signal is sent.
Gens Under Voltage
Warning
It is the generator’s A/B/C phase low voltage alarm value.
Gens Over Voltage
Warning
It is the generator’s A/B/C phase high voltage alarm value.
Gens Under Frequency
Warning
When generator’s frequency is lower than the value (not
equal to “0”) for 5s, alarm signal is sent.
Gens Over Frequency
Warning
When generator’s frequency is over the value and
continues for 1s, alarm signal is sent.
0 Disabled; 1 Pre-warn; 2 Electrical Trip; 3 Shutdown
When the load power is under the value and continues for
less than the delay value, alarm signal is sent. The return
value and delay value can also be set.
CAUTION! The value in first line of “Number” column is for GEC6120D and the value in brackets is for
GEC6110D.