Steam Trap
BK 15
Original Installation Instructions
810682-04

Questions and Answers

  • A
    Allen CastilloAug 11, 2025
    What to do if fluid escapes (equipment is leaking) from GESTRA Industrial Equipment?
    • M
      Miranda HernandezAug 11, 2025
      If fluid is escaping from the equipment, it could be due to several reasons: * The equipment or the body is damaged, in which case you should replace the equipment with a new one. * A gasket is damaged, then replace the gasket with a new one and clean gasket seating surfaces. * The connections are not tight, so provide the connections with leakproof seals.
  • K
    kimberlycohenAug 17, 2025
    How to increase the discharge capacity of GESTRA Industrial Equipment?
    • M
      Matthew SolomonAug 17, 2025
      The discharge capacity might be too low because the equipment is undersized. To resolve this, use equipment with a larger discharge capacity. Also, the differential pressure could be too small, so increase the steam pressure, lower the pressure in the condensate line, and consider using equipment with a larger discharge capacity, or a pump steam trap or a condensate return unit. Insufficient deaeration can also cause this, so connect an additional air vent.
  • A
    Alexander WarrenAug 22, 2025
    What to do if the discharge capacity is too low in GESTRA Industrial Equipment due to fluctuating steam pressure?
    • E
      Erica JenningsAug 23, 2025
      If the steam pressure and condensate flowrate fluctuate considerably, causing the discharge capacity to be too low, use equipment with a larger discharge capacity. If necessary, use a pump steam trap or a condensate return unit.
  • L
    lhartmanAug 28, 2025
    Why is fluid escaping from my GESTRA Industrial Equipment?
    • V
      vschmidtAug 29, 2025
      Fluid might be escaping because the body has been damaged by corrosion or erosion. Replace the equipment with a new one and use equipment made of material that is suitable for the application. Alternatively, the equipment has been damaged by waterhammer, so replace the equipment with a new one and take appropriate measures to protect the equipment against waterhammer, such as using non-return valves or a pump steam trap. Another possible cause is that the equipment has been damaged by frost, so replace the equipment with a new one, and when shutting down the installation make sure that all lines and the equipment are completely drained.
  • D
    Douglas HarperSep 4, 2025
    How to fix low discharge capacity in GESTRA Industrial Equipment due to pipe issues?
    • B
      Beth ColeSep 4, 2025
      If the pipes do not have a continuous fall in flow direction, this can cause the discharge capacity to be too low. Make sure that the lines run with a continuous fall in flow direction.