13
Freezing moisture in the
throttling device. After
switching off the throttling
device for 3-4 hours and then
switching on, or heating the
throttling device at the
evaporator entrance, the
systems works as intended.
After switching compressor,
the refrigerant babbles in the
spot where capillary tube
enters the evaporator.
Dehydrate the system with the
technological dehydrating filter.
Vacuum the refrigerating system
before refilling it. If this does not
solve the problem, replace the
compressor.
Capillary tube clogged up.
After switching off the
compressor, the refrigerant
does not babble at the
evaporator entrance. Thermal
cutout switches off the
compressor.
Replace the dehydrating filter, cut
off 50mm of the capillary tube on
the dehydration filter side. Is this
does not fix the defect, replace the
capillary tube.
Dehydrating filter is fully
clogged up. Increased power
consumption. The condenser
is cold.
Replace the dehydrating filter.
6. The compressor works almost
non-stop; duty cycle factor is
above 0,95.
The doors are being opened
for a prolonged period of
time.
Instruct the service personnel.
Doors yawn.
Make sure there are no yawns
between the door seal and the
doorframe.
7. Increased noise level and
rattling.
The device is in unstable
position.
Calibrate the device's position.
Pipelines touch the frame and
each other.
Distance the pipelines, carefully
bending them in the touch area.
The fan electric engine makes
noise while working.
Calibrate the fan blades.
8. Touching metal parts causes a
tingling sensation.
Faulty grounding circuit.
Immediately disconnect the device
from the power grid. Check the
grounding circuit.
9. Increased power consumption.
The device is loaded
incorrectly.
Load the device as per manual
requirements.
The air cannot access the
condenser.
Allow the air access to the
condenser.
10. The illuminating lamp is off.
Break in electrical circuit for
lighting.
Check the feed circuit and fix the
connection.
The driver (power source) for
LED illumination has burned
out.
Replace the driver (power source).
LED bulb has burned out.
Replace the LED bulb.