Chapter 5 Parameters
_
VFD-E Series
Revision August 2006, 01EE, SW--PW V1.03/CTL V2.03 5-63
 The multi-function input terminals are falling-edge triggered. For standard AC motor drive
(without extension card), there are MI1 to MI6 and Pr.04.26 will display 63 (111111) for no
action.
12345 0
0=Active
1=off
MI1
MI2
MI3
MI4
MI5
MI6
Weights
Bit
 For Example:
If Pr.04.26 displays 52, it means MI1, MI2 and MI4 are active.
The display value 52= 32+16+4 =1 X 2
5
+ 1X 2
4
+ 1X 2
2
= bit 6 X 2
5
+ bit 5 X 2
4
+ bit 3 X 2
2
01011100 0
0=Active
1=Off
MI1
MI2
MI3
MI4
MI5
MI6
MI7
MI8
MI9
Weights
Bit
 When extension card is installed, the number of the multi-function input terminals will increase
according to the extension card. The maximum number of the multi-function input terminals is
shown as follows.