Chapter 5 Parameters
_
VFD-E Series
Revision August 2006, 01EE, SW--PW V1.03/CTL V2.03 5-105
Group 11: Parameters for Extension Card
Make sure that the extension card is installed on the AC motor drive correctly before using group 11
parameters. See Appendix B for details.
11.00
Multi-function Output Terminal MO2/RA2
11.01
Multi-function Output Terminal MO3/RA3
11.02
Multi-function Output Terminal MO4/RA4
11.03
Multi-function Output Terminal MO5/RA5
11.04
Multi-function Output Terminal MO6/RA6
11.05
Multi-function Output Terminal MO7/RA7
Settings 0 to 21 Factory Setting: 0
Settings Function Description
0
No Function
1 AC Drive Operational
Active when the drive is ready or RUN command is “ON”.
2
Master Frequency
Attained
Active when the AC motor drive reaches the output
frequency setting.
3 Zero Speed
Active when Command Frequency is lower than the
Minimum Output Frequency.
4 Over-Torque Detection
Active as long as over-torque is detected. (Refer to Pr.06.03
~ Pr.06.05)
5
Baseblock (B.B.)
Indication
Active when the output of the AC motor drive is shut off
during baseblock. Base block can be forced by Multi-function
input (setting 09).
6 Low-Voltage Indication
Active when low voltage (Lv) is detected.
7
Operation Mode
Indication
Active when operation command is controlled by external
terminal.
8 Fault Indication
Active when a fault occurs (oc, ov, oH, oL, oL1, EF, cF3,
HPF, ocA, ocd, ocn, GFF).
9
Desired Frequency
Attained
Active when the desired frequency (Pr.03.05) is attained.
10
Terminal Count Value
Attained
Active when the counter reaches Terminal Count Value.
11
Preliminary Count Value
Attained
Active when the counter reaches Preliminary Count Value.