Chapter 5 Parameters
_
VFD-E Series
5-106 Revision August 2006, 01EE, SW--PW V1.03/CTL V2.03
Settings Function Description
12
Over Voltage Stall
supervision
Active when the Over Voltage Stall function operating
13
Over Current Stall
supervision
Active when the Over Current Stall function operating
14
Heat Sink Overheat
Warning
When heatsink overheats, it will signal to prevent OH turn off
the drive. When it is higher than 85
o
C (185
o
F), it will be ON.
15 Over Voltage supervision
Active when the DC-BUS voltage exceeds level
16 PID supervision
Active when the PID function is operating
17 Forward command
Active when the direction command is FWD
18 Reverse command
Active when the direction command is REV
19
Zero Speed Output
Signal
Active unless there is an output frequency present at
terminals U/T1, V/T2, and W/T3.
20
Communication Warning
(FbE,Cexx, AoL2, AUE,
SAvE)
Active when there is a Communication Warning
21
Brake Control (Desired
Frequency Attained)
Active when output frequency tPr.03.14. Deactivated when
output frequency dPr.03.15 after STOP command.
11.06 Multi-function Input Terminal (MI7)
11.07 Multi-function Input Terminal (MI8)
11.08 Multi-function Input Terminal (MI9)
11.09 Multi-function Input Terminal (MI10)
11.10 Multi-function Input Terminal (MI11)
11.11 Multi-function Input Terminal (MI12)
Settings 0 to 23 Factory Setting: 0
Settings Function Description
0 No Function
Any unused terminals should be programmed to 0 to insure they
have no effect on operation.
1
Multi-Step Speed
Command 1
2
Multi-Step Speed
Command 2
These four inputs select the multi-speed defined by Pr.05.00 to
Pr.05.14 as shown in the diagram at the end of the table in
Pr.04.08.