Chapter 5 Parameters
VFD-E Series
5-40 Revision August 2006, 01EE, SW--PW V1.03/CTL V2.03
These parameters determine the increase/decrease of the master frequency when operated
via the Multi-function Inputs when Pr.04.05~Pr.04.08 are set to 10 (Up command) or 11
(Down command).
02.11 aKeyboard Frequency Command Unit: 0.01
Settings 0.00 to 600.0Hz Factory Setting: 60.00
This parameter can be used to set frequency command or read keypad frequency command.
02.12 aCommunication Frequency Command Unit: 0.01
Settings 0.00 to 600.0Hz Factory Setting: 60.00
This parameter can be used to set frequency command or read communication frequency
command.
02.13
The Selections for Saving Keypad or Communication Frequency
Command
Factory Setting: 0
Settings 0 Save Keypad & Communication Frequency
1 Save Keypad Frequency only
2 Save Communication Frequency only
This parameter is used to save keypad or RS-485 frequency command.
02.14
Frequency Command Selections at Stop (for Keypad and
Communication)
Factory Setting: 0
Settings 0 By Current Freq Command
1 By Zero Freq Command
2 By Frequency Display at Stop
02.15 Frequency Display at Stop Unit: 0.01
Settings 0.00 ~ 600.0Hz Factory Setting: 60.00
These parameters are used to determinate the frequency at stop:
When setting Pr.02.14 to 0: the frequency at stop will be current frequency.
When setting Pr.02.14 to 1: the frequency at stop will be 0.
When setting Pr.02.14 to 2: the frequency at stop will be Pr.02.15.
02.16 Display the Master Freq Command Source
Settings Read Only Factory setting: ##