Chapter 5 Parameters
VFD-E Series
Revision August 2006, 01EE, SW--PW V1.03/CTL V2.03 5-47
Settings Read Only Factory setting: ##
Bit0=1: AFM used by PLC
The equivalent 1-bit is used to display the status (used or not used) of each analog output.
The value that Pr.03.10 displays is the result after converting 1-bit binary into decimal value.
0
Weights
Bit
0=no use
1=Used by PLC
AFM
For Example:
If Pr.03.10 displays 1, it means that AFM is used by PLC.
03.11 Brake Release Frequency Unit: 0.01
Settings 0.00 to 600.0Hz Factory Setting: 0.00
03.12 Brake Engage Frequency Unit: 0.01
Settings 0.00 to 600.0Hz Factory Setting: 0.00
These two parameters are used to set control of mechanical brake via the output terminals
(Relay or MO1) when Pr.03.00~03.01 is set to 21. Refer to the following example for details.
Example:
1. Case 1: Pr.03.12 t Pr.03.11
2. Case 2: Pr.03.12 d Pr.03.11
Case 1: Pr.03.12
Case 2: Pr.03.12
Pr. 03.11
Frequency
Output
Time
Run/Stop
Case 1: MO1=21
Case 2: MO1=21
Note: MO1: setting value of Pr.03.01
03.13 Display the Status of Multi-function Output Terminals
Settings Read Only Factory setting: ##
Bit0: RLY Status
Bit1: MO1 Status