APR 2017 GFS-520a (Formerly A-58)
EXTENDED
QUICK RESPONSE
AUTOMATIC SPRINKLERS
GL SERIES DRY TYPE
HORIZONTAL SIDEWALL
DESCRIPTION AND OPERATION
RECESSED
SPRINKLER TEMPERATURE RATING/CLASSIFICATION and COLOR CODING
Water Working Pressure Rating - 175 psi (12 Bars)
Factory tested hydrostatically to 500 psi (34 Bars)
Maximum low temperature glass bulb rating is -67°F (-55°C)
Frame - bronze De ector - brass Screw - brass
Bulb Seat - brass Spring - nickel alloy Seal - te on
Retainer - brass Pin - stainless steel
Torsion Spring - stainless steel Ori ce Insert - brass
Bulb - glass with alcohol based solution, 3mm size
3/4”NPT or 1”NPT Outer Tube - galvanized steel pipe
Inner Tube - stainless steel
TECHNICAL DATA
See reverse side for Approvals and Speci cations.
Temperature Ratings -
135°F (57°C), 155°F (68°C), 175°F (79°C)
200°F (93°C), 286°F (141°C)
SLEEVE & SKIRT
SURFACE MOUNT
CLASSIFICATION
AVAILABLE SPRINKLER
TEMPERATURES
BULB COLOR
N.F.P.A. MAXIMUM CEILING
TEMPERATURE
ORDINARY
INTERMEDIATE
HIGH
135°F/155°F
175°F/200°F
286°F
57°C/68°C
79°C/93°C
141°C
ORANGE/RED
YELLOW/GREEN
BLUE
100°F
150°F
225°F
38°C
66°C
107°C
The Globe Quick Response GL Series Dry Type Horizontal Sidewall
Sprinkler is designed for use in special applications such as freezing
environments and conditions where sediment or foreign materials might
accumulate in ordinary horizontal pipe nipples.
The Globe Quick Response GL Series Dry Type Horizontal Sidewall
Sprinkler utilizes a 3mm frangible glass ampule as the thermosensitive
element. This provides sprinkler operation approximately six times
faster than ordinary sprinklers. At the ampule's rated temperature,
the sprinkler opens releasing the bulb seat, causing the inner tube
assembly to move, allowing the spring assembly to pivot alongside
the inner tube. At this time, water ows through the sprinkler and is
distributed by the de ector, in an approved discharge pattern. It can be
installed wherever standard spray sprinklers are speci ed but offers the
additional feature of greatly increased safety to life. Quick Response
Sprinklers should be used advisedly and under the direction of approv-
ing authorities having jurisdiction.
The heart of Globe's GL Series sprinkler proven actuating assembly
is a hermetically sealed frangible glass ampule that contains a precisely
measured amount of uid. When heat is absorbed, the liquid within
the bulb expands increasing the internal pressure. At the prescribed
temperature the internal pressure within the ampule exceeds the
strength of the glass causing the glass to shatter. This results in water
discharge which is distributed in an approved pattern.

Other manuals for Globe GL Series

Question and Answer IconNeed help?

Do you have a question about the Globe GL Series and is the answer not in the manual?

Summary

DESCRIPTION AND OPERATION

Product Overview

Explains the GL Series Dry Type Horizontal Sidewall Sprinkler's design and application in special environments.

Operating Mechanism

Details the 3mm glass ampule and how heat triggers the sprinkler's water discharge mechanism.

TECHNICAL DATA

Performance Specifications

Lists temperature ratings, pressure limits, and low-temperature capabilities of the sprinkler.

Material Composition

Details the materials used for the sprinkler's frame, deflector, and various internal components.

Temperature Classification and Color Coding

Summarizes sprinkler temperature ratings with associated bulb colors and maximum ceiling temperatures.

SPECIFICATIONS AND APPROVALS

Product Specifications

Details SIN models, K-factors, thread sizes, lengths, and available finishes for sprinklers.

Approvals and Certifications

Lists hazard classifications, temperature approvals (FM, cULus), and spacing requirements.

Sprinkler Styles and Dimensions

Illustrates cross-sections of Extended, Recessed, Sleeve & Skirt, and Surface Mount sprinkler styles.

INSTALLATION AND ORDERING

Important Installation Guidance

Provides critical advice on sprinkler installation, tool usage, and potential damage from excessive force.

Ordering Information

Lists essential details to specify when ordering sprinklers, including accessories.

Product Warranty

Outlines the terms of Globe's product warranty and directs users to the Price List for details.

Overview

The Globe Quick Response GL Series Dry Type Horizontal Sidewall Sprinkler is designed for use in specific environments where freezing conditions are present, or where sediment and foreign materials might accumulate within ordinary horizontal pipe nipples. This sprinkler is engineered to provide rapid activation in the event of a fire.

At the core of the GL Series sprinkler's operation is a 3mm frangible glass ampule, which serves as the thermosensitive element. This innovative design allows the sprinkler to operate approximately six times faster than traditional sprinklers. When the ampule reaches its rated temperature, the fluid inside expands, increasing internal pressure until the glass shatters. This rapid response mechanism ensures that water discharge begins quickly, distributing water in an approved pattern to suppress the fire.

Upon activation, the shattering of the glass ampule releases the bulb seat, which in turn causes the inner tube assembly to move. This movement allows the spring assembly to pivot alongside the inner tube, opening the sprinkler and enabling water to flow through it. The water is then distributed by the deflector in a pattern designed for effective fire suppression. While these sprinklers can be installed wherever standard spray sprinklers are specified, their quick response capability significantly enhances safety to life. It is important that Quick Response Sprinklers are used judiciously and under the guidance of approving authorities with jurisdiction.

The GL Series Dry Type Horizontal Sidewall Sprinkler is constructed with durable materials to ensure reliability and longevity. The frame is made of bronze, while the deflector and screw are brass. The bulb seat is also brass, and the spring is nickel alloy. A teflon seal ensures a tight closure, and the retainer is brass with a stainless steel pin. A stainless steel torsion spring and a brass orifice insert further contribute to the sprinkler's robust design. The bulb itself is made of glass and contains an alcohol-based solution. The sprinkler is available with either a 3/4" NPT or 1" NPT connection, and features a galvanized steel outer tube and a stainless steel inner tube.

For proper installation, Globe GL Series Dry Pendent Sprinklers must adhere to the requirements outlined in NFPA 13. These sprinklers are designed to be installed by applying a pipe wrench to the outer tube. In situations where this is not feasible, a dedicated sprinkler head wrench may be used, with extreme caution, especially for lengths up to approximately 18 inches. Applying excessive force during installation can distort the frame, potentially rendering the unit inoperable.

When integrating this sprinkler into a wet system that extends into a freezing area, it is crucial to consult the Dry Caution Sheet for information regarding the minimum exposed barrel length required to prevent ice plugs. This sheet also provides additional critical installation data to ensure optimal performance and safety.

The GL Series sprinklers are available in various temperature ratings, including 135°F (57°C), 155°F (68°C), 175°F (79°C), 200°F (93°C), and 286°F (141°C). Each temperature rating is associated with a specific bulb color: orange/red for 135°F/155°F, yellow/green for 175°F/200°F, and blue for 286°F. These color codes correspond to N.F.P.A. maximum ceiling temperatures, ensuring compliance with safety standards. The sprinkler is designed to operate effectively within a water working pressure rating of 175 psi (12 Bars) and is factory tested hydrostatically to 500 psi (34 Bars). The maximum low temperature glass bulb rating is -67°F (-55°C), ensuring its resilience in extremely cold conditions.

The Globe Product Warranty covers any of its manufactured products found to be defective in material or workmanship for a period of one year from the date of shipment. For comprehensive details regarding the warranty, customers should refer to the Price List Terms and Conditions of Sale.

When ordering, it is important to specify the quantity, model number, style, orifice size, temperature rating, and desired finishes. Additionally, customers should specify the quantity of wrenches (P/N 333010), recessed wrenches (P/N 337014), protective caps (P/N 327109-cap for friction fit recessed), and desired escutcheons. The "A" Dimension, which represents the distance from the face of the fitting to the finished ceiling line, regardless of the escutcheon used, should also be provided. This detailed ordering process ensures that the correct components are supplied for each specific application.

Globe GL Series Specifications

General IconGeneral
CategoryIrrigation System
MaterialPlastic
Installation TypePop-up
Nozzle OptionsMultiple
Adjustable ArcYes
Adjustable RadiusYes
SeriesGL Series