10.6 Flue Length
The maximum permissable horizontal ue length is 8 metres
plus the ue terminal assembly, this can be achieved by use
of the accessories, see diagram 10.13.
However should additional 90º or 2 x 45º elbows be used then
the length MUST be reduced by 1metre.
The diagram 10.11 shows the length achievable by using the
kit A2043400.
When extension pipes are used the ue system must be
designed to have a continuous fall to the boiler of at least 2.5º
44mm/metre to allow condensate to run back into the boiler
and out via the condensate drain.
The ue can be installed from inside the building, when
access to the outside wall face is not practicable.
10 Standard Flue - Length, Preparation and Installation
Diagram 10.11
14015
14006
Standard Horizontal Flue