BUTT JOINT
BUTT JOINT
10.2 Horizontal Telescopic Flue - A2043600
Refer to diagram 10.2 for kit contents.
10.3 REAR Flue
If a wall thickness is between 203mm min. to 413mm max.
then the flue can be used without extensions.
With the flue elbow temporarily fitted, measure the distance
from the outside wall to the butt joint, see diagram 10.4. If
the measurement ‘Y’ exceeds 525mm, then the appropriate
length of extension pipe is r
equired.
If the dimension is less than 315mm DO NOT cut the flue, it
can project to a maximum of 600mm, refer to diagram 10.5. If
this is not desirable then a Standard flue MUST be used and
cut to length.
10.4 SIDE Flue
With the flue elbow temporarily fitted, measure the distance
from the outside wall to the butt joint, see diagram 10.6. If
the measurement ‘Y’ exceeds 525mm, then the appropriate
length of extension pipe is required.
If the dimension is less than 315mm DO NOT cut the flue, it
can project to a maximum of 600mm, refer to diagram 10.5. If
this is not desirable then a Standard flue MUST be used and
cut to length.
Diagram 10.4
13223
Diagram 10.5
12979
10 Telescopic Flue - Length, Preparation and Installation
Diagram 10.6
13224