Termination Boards for Tricon & Tricon CX G.M. International ISM0452-6
3
Warning
Termination Boards are installed onto standard EN/IEC60715 TH 35 DIN-Rail located in Safe Area or Zone 2, Group IIC, Temperature T4 Hazardous Area within the specified operating
temperature limits Tamb -40 to +70 °C. Termination Boards must be installed, operated and maintained only by qualified personnel, in accordance to the relevant national/international
installation standards (e.g. EN/IEC60079-14 Electrical apparatus for explosive gas atmospheres - Part 14: Electrical installations in hazardous areas (other than mines)), following the
established installation rules. De-energize power source (turn off power supply voltage) before plugging or unplugging the terminal blocks when installed in Hazardous Area or unless
area is known to be nonhazardous.
Warning: substitution of components may impair suitability for Zone 2/Division 2. Avertissement: la substitution des composants peut nuire à l’aptitude à la Zone 2/Div. 2.
Explosion Hazard: to prevent ignition of flammable or combustible atmospheres, disconnect power before servicing or unless area is known to be nonhazardous.
Danger d'Explosion: pour prévenir une inflammation de l'atmosphère inflammable ou combustible, couper l'alimentation avant de réparer à moins de savoir que
l'emplacement n'est pas dangereux.
Failure of a proper installation or use of the equipment may risk to damage the unit or severe personal injury.
Termination boards cannot be repaired by the end user and must be returned to the manufacturer or his authorized representative. Any unauthorized modification must be avoided.
Start-up
Before powering the unit check that all wires are properly connected, particularly supply conductors and their polarity.
Check conductors for exposed wires that could touch each other causing dangerous unwanted shorts.
Turn on power, the “PWR 1” and/or “PWR 2” green LED must be lit.