The micro-levelling, using an auxiliary motor/pump group (Ma) with reduced dimensions and capacity, allows
a lower power consumption and a shorter response time, compared to the traditional levelling/re-levelling
system.
The card, with the inputs V3 and VS on the X4 connector and the output signals RUN/UP and RDY performs
the micro-levelling using the following sequence (that it’s not the standard travel sequence):
3. V3 => ON
4. VS=> ON simultaneous or delayed (compared to V3 = ON)
5. RDY => OFF
6. RUN / UP => ON ok to start the micro-levelling motor
7. VS => OFF.
8. RUN / UP=> OFF
9. RDY => ON