Product SPecificationS
4 www.goodmanmfg.com SS-GMVC95
GMVc95 diMenSionS
MiniMuM clearanceS to coMbuStible MaterialS
Position Sides Rear Front Bottom Flue Top
Upow 0” 0” 3” C 0” 1”
Horizontal 6” 0” 3” C 0” 6”
C = If placed on combustible oor, the oor MUST be wood ONLY.
Notes:
• Forservicingorcleaning,a24”frontclearanceisrequired.
• Unitconnecons(electrical,ueanddrain)maynecessitategreaterclearancesthantheminimumclearanceslistedabove.
• Inallcases,accessibilityclearancemusttakeprecedenceoverclearancesfromtheenclosurewhereaccessibilityclearancesaregreater.
Model A B C D E
GMVC950453BX 17½” 16” 13⅛” 12⅛” 13⅝”
GMVC950704CX 21” 19½” 16⅛” 16 17½”
GMVC950905CX 21” 19½” 16⅛” 16 17½”
GMVC950905DX 24½” 19½” 16⅛” 16 17½”
GMVC951155DX 24½” 23” 20⅝” 19⅜” 20⅞”
Notes:
• InstallermustsupplyoneortwoPVCpipes:oneforcombusonair(oponal)andonefortheueoutlet(required).Ventpipemustbeeither2”or3”
indiameter,dependinguponfurnaceinput,numberofelbows,lengthofrunandinstallaon
(1or2pipes).TheoponalCombusonAirPipeisdependentoninstallaon/coderequirementsandmustbe2”or3”diameterPVC.
• Linevoltagewiringcanenterthroughtherightorlesideofthefurnace.Low-voltagewiringcanenterthroughtherightorlesideoffurnace.
• Conversionkitsforhigh-altudenaturalgasoperaonareavailable.ContactyourGoodmandistributorordealerfordetails.
• Installermustsupplyfollowinggaslinengs,accordingtowhichentranceisused:
Le—Two90ºelbows,oneclosenipple,straightpipe
Right—Straightpipetoreachgasvalve
• Forboomreturn:Failuretounfoldangesmayreduceairowbyupto18%.Thiscouldresultinperformanceandnoiseissues.
28¾
19⅞
RIGHTSIDEVIEW
LEFTSIDEVIEW
22¹/₁₆
FOLDEDFLANGES
23⁹/₁₆
UNFOLDEDFLANGES
FRONTVIEW
FOLDED FLANGES
UNFOLDED FLANGES
D
E
11¾
30¼
¾
¾
30¼
11¾
32¹³/₁₆
19³/₁₆
24⁹/₁₆
2¹¹/₁₆
/₁₆
19³/₁₆
¾
21¼
2⅝
7⅜
1⅝
4⅛
16⅝
2⅝
27⅛
6⅛