Why is my Goodman GPH1624M41 Heat Pump not cooling enough?
- WWalter LoweryAug 12, 2025
If your Goodman Heat Pump isn't cooling sufficiently, first ensure the unit is properly sized for the area it's cooling by recalculating the load. Check for proper airflow, which should be approximately 400 CFM per ton. Verify the refrigerant charge by following the procedure attached to the unit service panel. Also, confirm that the voltage at the compressor terminals is within 10% of the nameplate volts when the unit is operating.