prodUCt SpECifiCationS
prodUCt SpECifiCationS
SS-SSX16 www.goodmanmfg.com 3
SpECifiCationS
SSX16
0241B*
SSX16
0301A*
SSX16
0361B*
SSX16
0421A*
SSX16
0481B*
SSX16
0591A*
Cooling Capacity
Nominal Cooling (BTU/h) 24,000 30,000 36,000 42,000 48,000 60,000
Decibels 73.5 73.5 73.5 75 74 73.5
Compressor
RLA 13.5 12.8 14.1 16.7 19.9 25.0
LRA 58.3 64 77 79 109 134
Condenser Fan Motor
Horsepower (RPM) 1/6 1/6 1/6 1/4 1/4 1/4
FLA 1.10 1.10 1.10 1.50 1.50 1.50
Refrigeration System
Refrigerant Line Size¹
Liquid Line Size (“O.D.) ⅜" ⅜" ⅜" ⅜" ⅜" ⅜"
Sucon Line Size (“O.D.) ¾" ¾" ⅞" 1⅛" 1⅛" 1⅛"
Refrigerant Connecon Size
Liquid Valve Size (“O.D.) ⅜" ⅜" ⅜" ⅜" ⅜" ⅜"
Sucon Valve Size (“O.D.) ¾" ¾" ¾" ⅞" ⅞" ⅞"
Valve Connecon Type Sweat Sweat Sweat sweat Sweat Sweat
Refrigerant Charge 97 96 102 109 138 251
Electrical Data
Voltage-Phase 208/230-1 208/230-1 208/230-1 208/230-1 208/230-1 208/230-1
Minimum Circuit Ampacity ² 18.0 17.1 18.7 22.4 26.4 32.8
Max. Overcurrent Protecon ³ 30 25 30 35 45 50
Min / Max Volts 197/253 197/253 197/253 197/253 197/253 197/253
Electrical Conduit Size ½" or ¾" ½" or ¾" ½" or ¾" ½" or ¾" ½" or ¾" ½" or ¾"
Ship Weight (lbs) 173 174 182 185 236 287
¹ Tested and rated in accordance with ARI Standard 210/240
² Wire size should be determined in accordance with Naonal Electrical Codes; extensive wire runs will require larger wire sizes
³ Must use me-delay fuses or HACR-type circuit breakers of the same size as noted.
Notes
• Always check the S&R plate for electrical data on the unit being installed.
• Installer will need to supply ⅞” to 1⅛” adapters for sucon line connecons.
• Unit is charged with refrigerant for 15’ of ⅜” liquid line. System charge must be adjusted per Installaon Instrucons Final Charge Procedure.
• Installaon of these units requires the specied TXV Kit to be installed on the indoor coil. THE SPECIFIED TXV IS DETERMINED BY THE OUTDOOR UNIT NOT
THE INDOOR COIL.