EasyManua.ls Logo

Grant Aerona HPAW110 - Page 25

Default Icon
50 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Electrical
21
230 Vac
Compressor
Heater
4-way
valve
Expansion Valve
Ret Gas Sensor
Ext Temp Sensor
Coil Temp Sensor
Dis Gas Sensor
Ret Temp Sensor
N
Compressor
Fan
motor
Pump
Relay
KM2
6kW
Electric
Element
Orange
Red
Blue
White
Blk
Power Supply
Terminal
3 Connection points for installer
ATC Controller
Socket
S-Plan Controls
Connections
3 2 1
3 2 1
12
11
10
9
8
7
6
5
4
3
2
1
24
23
22
21
20
19
18
17
16
15
14
13
C
R
S
24 Vac
Fuse
Relay KM1
Low pressure switch
High pressure switch
Figure 8-9: Heat pump connection diagram for 6kW electrical element
Model 3kW Immersion Heater 6kW Immersion Heater
MCB MCB MCB MCB
P
In
(W) I
Start
(A) I
Run
(A) V Hz I
Start
I
Run
(A) Type I
Start
I
Run
(A) Type
HPAW65 1620 22.09 7.36 220 50 35.09 20.36 32 D 49.09 34.36 40 D
HPAW85 2200 30.00 10.00 220 50 43.00 23.00 32 D 57.00 37.00 40 D
HPAW110 2610 35.59 11.86 220 50 48.59 24.86 32 D 62.59 38.86 40 or 50 D
HPAW130 2590 35.32 11.77 220 50 48.32 24.77 32 D 62.32 38.77 40 or 50 D
HPAW155 2770 37.77 12.59 220 50 50.77 25.59 32 D 64.77 39.59 50 D
Model 3kW Immersion Heater 6kW Immersion Heater
MCB MCB MCB MCB
P
In
(W) I
Start
(A) I
Run
(A) V Hz I
Start
I
Run
(A) Type I
Start
I
Run
(A) Type
HPAW65 1770 23.09 7.70 230 50 36.09 20.70 32 D 50.09 34.70 40 D
HPAW85 2404 31.36 10.45 230 50 44.36 23.45 32 D 58.36 37.45 40 D
HPAW110 2852 37.20 12.40 230 50 50.20 25.40 32 D 64.20 39.40 50 D
HPAW130 2830 36.91 12.30 230 50 49.91 25.30 32 D 63.91 39.30 50 D
HPAW155 3028 39.50 13.17 230 50 52.50 26.17 32 D 66.50 40.17 50 D
Assumptions: 1. 30m run from consumer box to heat pump
2. Cable not run in thermally insulated environment: Method A and C only (17th edition)
3. Starting current assumes 3x running current
4. Earth Loop Impedence value does not exceed 0.36W for a D type MCB
IMPORTANT: ENSURE INCOMING SUPPLY CABLE AND SUPPLY FUSE ARE OF SUITABLE SIZE
The 6kW immersion
element is ONLY available
as a factory fitted option

Related product manuals