15
PHOTOVOLTAIC MODULES SAFETY
AND INSTALLATION MANUAL Rev. L
VALID IN NORTH AMERICA ONLY
1305 South Bertelsen Road, Eugene, Oregon 97402, USA
www.grapesolar.com
Tel: 1-877-264-1014 (toll free), 1-541-349-9000, Fax: 1-541-343-9000
Table-1. PV Module Electrical Specification
Max
Power
Voltage
Vmp (V)
Max
Power
Current
Imp (A)
Open
Circuit
Voltage
Voc (V)
Short
Circuit
Current
Isc (A)
Max
System
DC
Voltage
(V)
GS-S-175-EUG 175 36.2 4.83 43.8 5.28 0.02 -0.34 -0.48
GS-S-180-EUG 180 36.5 4.93 44.2 5.35 0.02 -0.34 -0.48
GS-P-1 60-EUG 160 23.3 6.87 28.6 7.57
GS-P-1 65-EUG 165 23.5 7.02 28.8 7.70
GS-P-1 70-EUG 170 23.8 7.15 29.0 7.82
GS-P-1 75-EUG 175 24.0 7.29 29.2 7.96
GS-P-1 80-EUG 180 24.1 7.47 29.4 8.10
GS-P-1 90-EUG 190 26.7 7.12 32.6 7.80
GS-P-1 95-EUG 195 26.9 7.25 32.8 7.92
GS-P-2 00-EUG 200 27.1 7.38 33.0 8.02
GS-P-2 05-EUG 205 27.2 7.54 33.2 8.15
GS-P-2 20-EUG 220 30.0 7.33 36.6 7.98
GS-P-2 25-EUG 225 30.1 7.48 36.8 8.10
GS-P-2 30-EUG 230 30.3 7.60 37.0 8.20
GS-P-2 60-EUG 260 35.8 7.26 43.7 7.92
GS-P-2 65-EUG 265 36.0 7.36 43.9 8.00
GS-P-2 70-EUG 270 36.1 7.48 44.1 8.10
GS-P-2 75-EUG 275 36.2 7.60 44.3 8.20
GS-P-2 80-EUG 280 36.4 7.70 44.5 8.28
NOTES: The electrical characteristics are within ±10 percent of indicated values of Isc, Voc, and Pmax under standard test conditions (irradiance of
1kW/m
2
, AM1.5 spectrum, and cell temperature of 25℃). Photovoltaic modules may produce more current and /or voltage than reported at standard
test conditions. Accordingly, the values of Isc and Voc marked on the module should be multiplied by a factor of 1.25 when determining component
voltage ratings, conductor ampacities, fuse sizes, and sizes of regulators which are connected to the PV output. Refer to Section 690-8 of the National
Electrical Code for an additional multiplying factor of 125 percent (80 percent derating) which may be applicable.