Remote Controller Function Manual
 6.1.1 Temperature Parameters 
 Indoor preset temperature (T
preset
) 
Indoor ambient temperature (T
amb.
) 
6.1.2 Basic Functions 
 Under any mode, the compressor, once started, will not be stopped within 6 minutes . 
 
Once Stopped, the compressor should in no way be restarted unless 3-minute lag.  
  
6.1.2.1 Cooling Mode 
6.1.2.1.1 Cooling Conditions and Process 
+1℃, the unit will run under cooling mode, in which case the compressor and outdoor fan will be 
started, the indoor fan will run at preset speed. 
When T
amb.
≥T
preset
When T
 amb
≤T
preset
 -1 , the unit will be stopped under cooling mode,℃  in which case the compressor and outdoor fan will be 
stopped and the indoor fan will run at preset speed. 
When T
preset
 -1 <T℃
 amb.
< T
preset
 +1 , the unit will maintain its original operating status.℃  
  Under this mode, the reversal valve will be de-energized and the temperature can be set from 16 to 30℃. 
T
preset
 
+1℃ 
T
preset
 
-1℃ 
Start Cooling 
Original operating status 
Stop cooling 
Compressor 
Outdoor fan 
Indoor fan 
6 min. 
6 min. 
3 min. 
Preset speed
 
Stop 
Run 
T
amb
 
6.1.2.2 Dehumidifying Mode 
6.1.2.2.1  Dehumidifying Cooling Conditions and Process 
preset
> T
 amb.
When T 
+2 , the unit will run under dehumidify cooling mode, in which case the compressor and outdoor fan ℃
will be started and the indoor fan will run at preset speed. 
When T
preset
 -2℃≤T
 amb.
≤T
preset
 +2℃, the unit will run under dehumidifying mode, in which case the indoor fan will run at 
low speed. After the compressor and outdoor fan has run 6 minutes, the compressor will be stopped, the outdoor fan will 
be stopped after 15-second lag and the indoor fan will be stopped after 30 seconds. After 3.5 minutes, the compressor 
and outdoor fan will be started, and the indoor fan will run at low speed. The dehumidifying process is so repeated in 
cycle.  
When T
amb
.< T
preset
-2℃, the compressor, outdoor fan and indoor fan will be stopped. 
T
amb
 
Cooling 
Stop cooling 
Compressor 
Outdoor fan 
Indoor fan 
Run 
Stop 
Dehumidifying 
Preset
speed 
T
preset
 +2℃ 
T
preset
 -2℃
 
Low speed 
Low speed 
6 min. 
6 min. 
4 min. 
4 min. 
Run 
  Under this mode, the reversal valve will be de-energized and the temperature can be set from 16 to 30℃.