Enginnering Data
18
Horizontal concealed three-row-pipe FCU (G series, 208-230VAC 60Hz)
Model
Item
Unit
FP-34WA
S/G-D
FP-51WA
S/G-D
FP-68WA
S/G-D
FP-85WA
S/G-D
FP-102W
AS/G-D
FP-136W
AS/G-D
FP-170W
AS/G-D
FP-204W
AS/G-D
Performance
Air flow
High
/h
340
510
680
850
1020
1360
1700
2040
Medium
248
394
495
638
788
1095
1275
1575
Low
173
263
330
425
525
730
850
1050
Cooling
capacity
High-speed
W
2250
3300
4400
5200
6600
8300
10200
12200
Heating
capacity
High-speed
W
3700
5400
7350
8500
10650
13500
17000
20000
Water flow
/h
0.39
0.57
0.76
0.90
1.14
1.43
1.76
2.10
Water resistance
kPa
20
21
22
30
35
40
33
40
Noise
12pa
dB(A)
35
39
41
43
46
46
48
50
30Pa
38
40
44
46
48
49
50
52
ESP
Pa
12Pa for the standard type (without the air diffuser and filter)
30Pa for the high static pressure type
Coils
Type
Copper tube with lourved fins
Working pressure
≤1.6MPa
Motor
Type
Class B insulation, capacitor start
Quantity
Piece
1
2
Power lines
208-230VAC 60Hz
Protection class
IP20
Input power
12pa
W
36
63
70
104
114
182
180
228
30Pa
W
49
64
74
105
123
183
221
273
Power lines
mm
2
×piece
0.5×3
Anti electric shock class
I
Fan
Model
Forward multi-vane low-noise centrifugal fan
Quantity
piece
1
2
3
4
Connection pipe
Inlet
Rc3/4(inner thread)
Outlet
Rc3/4(inner thread)
Condensate
Rc3/4(outer thread)
Net weight
kg
11.6
13.4
14.7
16
17.4
24
26.6
28.5
Outline dimensions
Width
mm
680
800
900
1000
1080
1380
1520
Depth
mm
490
460
490
490
490
490
490
Height
mm
235
235
235
235
235
235
235
Thermostat (optional)
Mechanical
Z54352A1
Digital
WK-110PA0
Digital (deluxe)
WK-010PA-K-K
Notes:
a) The left and right modes can be switched over on site. The correction coefficient for both
cooling and heating is 0.9.
b) Nominal cooling conditions: (27/19.5
) indoor dry/wet bulb temperature, (7/12
) entering
and leaving water temperature. Nominal heating conditions: 21
indoor dry bulb
temperature, 60
entering water temperature.
c) The noise is tested under the semi-anechoic chamber and the actual value will change