Enginnering Data
22
Horizontal concealed FCU, standard (G series, 220~240VAC, 50Hz, EU)
Model
Item
Unit
FP-34WA
H/GHL-K
FP-51WA
H/GHL-K
FP-68WA
H/GHL-K
FP-85WA
H/GHL-K
FP-102WA
H/GHL-K
FP-136WA
H/GHL-K
FP-170WA
H/GHL-K
FP-204WA
H/GHL-K
Performa
nce
Air flow
High
m
3
/h
450
590
750
930
1100
1400
1700
2000
Medium
315
413
525
651
770
980
1190
1400
Low
220
290
367
455
539
686
833
980
Cooling
capacity
High
W
2000
3100
3550
4500
5200
6900
7200
10200
Heating
capacity
High
W
2300
3500
4500
4900
6300
8200
9200
12000
Water flow
m
3
/h
0.34
0.53
0.61
0.78
0.90
1.19
1.24
1.76
Water resistance
kPa
15
30
23
25
35
40
36
40
Noise
dB(A)
39
39
41
46
49
48
49
52
External static
pressure
Pa
0Pa
Coils
Type
Copper tube and lourved fins
Working pressure
1.6MPa
Motor
Type
Class B insulation, capacitor start
Quantity
piece
1
2
Power supply
220-240VAC 50Hz
Protection class
IP20
Input power
W
48
57
72
90
111
152
185
222
Power lines
mm
2
×
piece
0.5
×
3
Anti electric shock class
I
Fan
Type
Forward multiple-vane low-noise centrifugal fan
Quantity
piece
1
2
3
4
Connection pipe
Inlet
Rc3/4(inner thread)
Outlet
Rc3/4(inner thread)
Condensate
Rc3/4(external thread)
Net weight
kg
14.5
17
18.9
20.8
21.9
31.5
34.1
38
Outline
dimensions
Width
mm
680
800
900
1000
1080
1380
1520
1620
Depth
mm
500
500
500
500
500
500
500
500
Height
mm
235
235
235
235
235
235
235
235
Thermostat (optional)
Mechanical
Z54352A1
Digital
WK-110PA0
Digital (deluxe)
WK-010PA-K-K
Notes:
a) The left and right modes can be switched over on site. The correction coefficient for both
cooling and heating is 0.9.
b) Nominal cooling conditions: (27/19
) indoor dry/wet bulb temperature, (7/12
) entering
and leaving water temperature. Nominal heating conditions: 20
indoor dry bulb
temperature, 45
entering water temperature and 40
leaving water temperature.
c) The noise is tested under the semi-anechoic chamber and the actual value will change
under different environments.