Cassette Type FCU
21
5 Water leaks.
The condensate pipe is clogged. Clean the drain pipe.
The unit is not installed as required.
Adjust the unit and let the unit keep a
certain inclination degree.
The environmental air humidity is too
high.
Do humidication and do not let the
high-temperature and high-humidity
air coming into the room.
The fan stops but cold water is
supplied continuously.
Close the water dampers or run the
unit.
The discharge valve is not tightened. Tighten the discharge valve.