121 
  Back: 
Press “Back” key to the previous menu, and long press the “Back” key to exit the operation. 
③  Display unit 1(d1) operation: 
  When entering into the display unit 1: 
The function section display running code uninterrupted and the data section display the current value 
uninterrupted. 
  “+” “-”Keys are invalid in the operation. 
   “+” “-”Keys are invalid in the operation. 
④  If no operation is performed within 1min, it will automatically return to the normal display. 
1.3.3 The meaning of running code 
Sorts 
Function 
section 
Data section  Remarks 
Control Unit  CU  Blank 
 
Vacuum operation  AU  The current parameter 
Set refrigerant 
recovery mode 
Fo The current parameter 
Use the “+” “-” keys to switch ON, OF.
  ON represents that the unit is 
running the current state. 
  OF represents that the unit isnot 
running the current state. 
Display Unit 1 
d1 
Blank  
Display suction 
temperature 
NH 
Suction temperature. For 
example, 15 represents 15℃ 
Display discharge 
temperature 
NP 
Discharge temperature. For 
example, 70 represents 70℃ 
Display low pressure  PL 
Low pressure. For example, 95 
represents 0.95Mpa 
Display high 
pressure 
PH 
High pressure. For example, 
280 represents 2.80Mpa 
“+” “-”Keys are invalid in the operation. 
 
1.3.4 For example: How to Display low pressure 
①  Long press “Fuc” key for more than 2s to enter the first-level menu: the function section flashes “CU” 
code and the data section is blank. 
②  Switch with the “Fuc” key again: the function section flashes “d1” code and the data section is blank. 
③  Press “Enter” key to enter the second-level menu: the function section flashes “NH” code and the data 
section display the current suction temperature. 
④  Switch with the “Fuc” key to display low pressure: the function section flashes “PL” code and the data 
section display the current low pressure. 
 
1.3.5  How to Recover the refrigerant to the outdoor unit 
1)  Let all the indoor units work in the Cooling mode for more than half one hour. 
2)  Set the units running the “Fo” mode. 
①  Long press “Fuc” key for more than 2s to enter the first-level menu: the function section flashes “CU” 
code and the data section is blank. 
②  Press “Enter” key to enter the second-level menu: the function section flashes “AU” code and the data 
section display the current parameters. 
③  Switch with the “Fuc” key until the function section flashes “Fo” code and the data section display the 
current parameters.