U-Match Series Service Manual
12
3.3.2 Indoor unit
Table 1-4-2 Electrical Data of Indoor Unit
Model
Power
Supply
Fan Motor
FLA
Fuse/Breaker
Capacity
Min. Power
Supply Cord
V/Ph/Hz
A
A
mm
2
GFH18K3HI
220-240,1,50
<1
5/6
1.0
GFH18K3H1I
220-240,1,50
<1
5/6
1.0
GFH24K3HI
220-240,1,50
<1
5/6
1.0
GFH24K3H1I
220-240,1,50
<1
5/6
1.0
GFH30K3HI
220-240,1,50
<1
5/6
1.0
GFH30K3H1I
220-240,1,50
<1
5/6
1.0
GFH36K3HI
220-240,1,50
<1
5/6
1.0
GFH36K3H1I
220-240,1,50
<1
5/6
1.0
GFH42K3HI
220-240,1,50
<1
5/6
1.0
GFH42K3H1I
220-240,1,50
<1
5/6
1.0
GFH48K3HI
220-240,1,50
<1
5/6
1.0
GFH48K3H1I
220-240,1,50
<1
5/6
1.0
GFH60K3HI
220-240,1,50
<1
5/6
1.0
GFH60K3H1I
220-240,1,50
<1
5/6
1.0
GKH18K3HI
220-240,1,50
<1
5/6
1.0
GKH24K3HI
220-240,1,50
<1
5/6
1.0
GKH30K3HI
220-240,1,50
<1
5/6
1.0
GKH36K3HI
220-240,1,50
<1
5/6
1.0
GKH42K3HI
220-240,1,50
<1
5/6
1.0
GKH48K3HI
220-240,1,50
<1
5/6
1.0
GKH60K3HI
220-240,1,50
<1
5/6
1.0
Notes:
RLA: Rated load amperes
LRA: Locked rotor amperes
FLA: Full load current
Install the disconnect device with a contact gap of at least 3mm in all poles nearby the units
(Both indoor unit and outdoor unit).The appliance must be positioned so that the plug is
accessible.
The specifications of the breaker and power cable listed in the table above are determined based
on the maximum power (maximum amps) of the unit.
The specifications of the power cable listed in the table above are applied to the conduit-guarded
multi-wire copper cable (like, YJV copper cable, consisting of PE insulated wires and a PVC
cable jacket) used at 40°С and resistible to 90°С (see IEC 60364-5-52). If the working condition
changes, they should be modified according to the related national standard.
The specifications of the breaker listed in the table above are applied to the breaker with the
working temperature at 40°С. If the working condition changes, they should be modified
according to the related national standard.